3CRV Three-phase current reset with a standard remote display
What's New
arrow AR360 AutoRANGER® Fault Indicators
arrow WS-LG1 Wireless Sensor
arrow 2010 Product Catalog
arrow ISO 9001:2000 Certificate
arrow Improve Grid Reliability With Wireless Fault Indication
arrow Improve Grid Reliability in Busy Urban Areas
arrow Schweitzer Engineering Laboratories, Inc. Becomes 100 Percent Employee- Owned
arrow Find Faults Faster on Paper-Insulated Lead Cable (PILC)
arrow RadioRANGER™ QuickStart Installation Guide
arrow Expanding the Benefits of the RadioRANGER™ to Pad-Mounted Enclosures
white arrow RadioRANGER™ Flyer
white arrow RadioRANGER™ Wireless Fault Indication System Reduces Fault- Locating Time
White Arrow AutoRANGER™ Test Certificate: ANSI/IEEE Std. 495-1986
White Arrow Reducing Customer Outage Duration at We Energies

 

 

 

  Home
  About Us
  Products
  Applications
arrow  Installation Instructions
  Events
  Contact Us
  News and Job Openings

E.O. Schweitzer Manufacturing
A Division of SEL

    Fault Indicators
    Voltage Indicators
    Other Products for the Industry

Tel.: 1-847-362-8304
Fax: 1-847-362-8396
Email: csr@eosmfg.com

 pdf Download LINAM CR Flyer

3CRV
Three-Phase Current Reset With a Standard Remote Display

Overview

SEL three-phase current reset fault indicators with standard remote displays (3CRV) use continuous line load current to automatically reset and to maintain the energy required to respond to a fault (no batteries or minimum voltage required). When a fault occurs, the 3CRV’s reflective red target appears. It automatically resets when minimum line load is restored. 3CRV fault indecators are easy to install on an energized system using hotsticks and are field testable using tool Cat. No. CRSRTT. Apply 3CRV fault indicators on systems that are three-phase sectionalized. A single integral split-core transformer powers the 3CRV. The other two phases monitor fault level current to activate a single remote display. The 3CRV fault indicator requires a minimum continuous load current to reset and remain ready to respond to a fault. The remote visual display assembly includes a panel mounting kit with a drilling template, polycarbonate display window, and associated stainless steel mounting hardware.

 

Applications

3CRV fault indicators are typically installed on underground systems near sectionalizing points. In three-phase feed-through transformers, install the indicators at the base of the connector on the underground cable. 3CRV indicators are ideal in three phase applications where test point type connectors are not available to install a voltage reset type indicator. In livefront switchgear applications, install one set of 3CRV fault locators on each outgoing feed. The phase sensors are installed below the stress relief terminator located in the pad or in the pedestal. The remote display load is then trained up to near the top of the cabinet for mounting at the optimum location. The 3CRV is also well suited to subsurface network switchgear or any three-phase elbow switching structure of wall-mounted switchgear. To keep the cables tidy and in place, EOS Manufacturing offers magnetic cable guides that securely position the cable but are easy to reposition when pulling elbows or working inside the enclosure.

SEL offers an optional auxiliary contact feature that can be used with the utilities' SCADA systems. This normally open latching-type contact closes when a fault occurs and will not open until normal system load current is restored for 30 continuous seconds.

A three-phase Current Reset Fault Indicator in a switchgear application. A three-phase Current Reset Fault Indicator in a switchgear application.

Specifications
Power Source Load current
Nominal Trip Ratings 400 & 800 A
Trip Tolerance +/- 10%
Voltage Range (P-G) 5 kV min. to 38 kV max.
Minimum Reset Current 3 A
Reset Automatic at minimum current
Maximum System Voltage Underground cable rating
Typical Reset Time 25 seconds at 3 A
Maximum Fault Current 25 kA for 10 cycles 60 Hz
Temperature Range -40° to +85°C
Trip Response Time 1 ms
Inrush Restraint Response Time 300 ms (add “IR” option)
Clamping Range 75” to 2.1” O.D.
Housing Material UV-stabilized polycarbonate resin
Standard Display (1.2 cmI target area) Reflective red target
Transformer Core Silicon steel with vinyl coating
Submersibility 15 feet
Weight 1250 grams (typical)

 