3CRV fault indicators are typically installed on underground systems near sectionalizing points. In three-phase feed-through transformers, install the indicators at the base of the connector on the underground cable. 3CRV indicators are ideal in three phase applications where test point type connectors are not available to install a voltage reset type indicator. In livefront switchgear applications, install one set of 3CRV fault locators on each outgoing feed. The phase sensors are installed below the stress relief terminator located in the pad or in the pedestal. The remote display load is then trained up to near the top of the cabinet for mounting at the optimum location. The 3CRV is also well suited to subsurface network switchgear or any three-phase elbow switching structure of wall-mounted switchgear. To keep the cables tidy and in place, EOS Manufacturing offers magnetic cable guides that securely position the cable but are easy to reposition when pulling elbows or working inside the enclosure.
SEL offers an optional auxiliary contact feature that can be used with the utilities' SCADA systems. This normally open latching-type contact closes when a fault occurs and will not open until normal system load current is restored for 30 continuous seconds.
A three-phase Current Reset Fault Indicator in a switchgear application.
|