1CRI Single-phase current reset indicator with integral display

What's New

arrow 2008 Product Catalog
white arrow RadioRANGER™ Flyer
white arrow RadioRANGER™ Wireless Fault Indication System Reduces Fault- Locating Time
White Arrow AutoRANGER™ Test Certificate: ANSI/IEEE Std. 495-1986
White Arrow Reducing Customer Outage Duration at We Energies
White Arrow Use FCIs With Other SEL Distribution Products to Increase Reliability
Overhead Fault Indicator Model Option Table
little arrow Fault Indicator Model Option and Part Number Tables
SEL LINAM Current Reset Fault Indicator Flyer
little arrow AutoRANGER Field Guide

 

 

 

  Home
  About Us
  Products
  Applications
arrow  Installation Instructions
  Events
  Sales Offices
  News and Job Openings

E.O. Schweitzer Manufacturing
A Division of SEL

    Fault Indicators
    Voltage Indicators
    Other Products for the Industry

Tel.: 1-847-362-8304
Fax: 1-847-362-8396
Email: csr@eosmfg.com

pdf Download LINAM CR Flyer

1CRI
Single-Phase Current Reset Indicator With an Integral Display

Overview SEL current reset fault indicators (1CRI) use the continuous line load current to automatically reset and to maintain the energy required to respond to a fault. When a fault occurs, the 1CRI trips and displays a reflective red target built directly into the phase-sensor itself. The target remains in the tripped position until minimum line load returns. Then, it automatically resets and returns to the untripped position. 1CRI fault indicators are easy to install on energized systems using hotsticks, and are field testable using tool No. CRSRTT.
Applications 1CRI fault indicators are typically applied on underground systems in padmounted enclosures. Installing devices at each sectionalizing location helps the linemen quickly locate the faulted cable section. Large industrial customers will also benefit from installing 1CRI fault indicators on their low-voltage secondary lines. The integral split-core current transformer clamp makes the E-1CRI easy to install under the elbow terminator or other separable connector.The standard 1CRI model requires a 3 A minimum continuous load current. The indicator’s 1 ms trip response time allows it to coordinate easily with current-limiting fuses.

The optional inrush restraint feature blocks the indicator from targeting because of recloser operations. When the protection operates, the indicator senses the loss of current flow and prohibits trip targeting until normal load current is restored.

SEL also offers an auxiliary contact option that provides a latching contact closure when a fault occurs. This contact allows 1CRI fault indicators to connect to SCADA systems, a feature that is becoming increasingly valuable as SCADA systems expand.

Specifications
Power Source Load current
Nominal Trip Ratings 400 & 800 A
Trip Tolerance +/- 10%
Minimum Reset Current 3 A (1.5 A option also available)
Reset Automatic at minimum current
Maximum System Voltage Underground cable rating
Typical Reset Time 25 seconds at 3 A
Maximum Fault Current 25 kA for 10 cycles at 60 Hz
Temperature Range -40° to +85°C
Trip Response Time 1 ms
Inrush Restraint 300 ms (add “IR” option)
Clamping Range 0.75” to 2.1” O.D.
Housing Material UV-stabilized polycarbonate resin
Display [1.2 cmI target area] Reflective red target
Transformer Core Silicon steel with vinyl coating
Submersibility 15 feet
Weight 560 grams (typical)

 