SEL BEACON® timed reset fault indicators are ideal for installation in transformers or switchgear. They do not require system voltage or load current to reset. 1BTRI fault indicators are especially useful in locating temporary faults: the display continues to flash until the end of the time-out period, providing plenty of time for a line crew to identify the location of the temporary fault.
Features
Standard version powered by a replaceable 3.6 V lithium battery (Specify option "N" for a 8.5Ah nonreplaceable battery with 3,000+ flashing hours)
No system voltage or load current necessary
High-intensity LED display is easy to spot both at night and during the day
The Snap Action Clamp option enables installation on larger cable diameters
UV-stabilized materials provide excellent weatherability
Compact, lightweight design simplifies installation and stocking
Specifications
Power Supply
3.6 V lithium battery
Battery Shelf Life
15 years
Average Flashing Hours
1.200
Nominal Trip Ratings
50 to 1200 A
Trip Tolerance
+/- 10%
Voltage Range
Matches the URD cable rating
Maximum Fault Current
25 kA for 10 cycles
Temperature Range
-40° to +85°C
Trip Response Time
1 ms
Clamping Range
0.25" to 1.6" O.D. (Please specify clamping diameter or range when ordering).